16 cjc selection, 16 cjc selection -14 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual
Page 21
IM 01C50T03-01E
3-14
3. OPERATION
USER CAL IGNORE : Ignore user trim value
and return to the
factory set value.
USER CAL ACT
: Use user trim value.
NOTE
Regardless of restarting the transmitter, the
“USER CAL ACT” is always set and the user
trim value is used as the input signal unless it is
cleared by “USER CAL CLEAR.”
3.2.16 CJC Selection
For thermocouple input, terminal temperature measured
by an internal sensor is used for Cold Junction Com-
pensation function. In YTA, a constant value set by
users can be used for the compensation function in
place of the terminal temperature. If the constant value
is set to “0", the compensation is not applied.
H01 : CJC SELECT
Select “Constant CJC” to use the constant value in
place of terminal temperature;
INTERNAL CJC
: Use the terminal tempera-
ture measured by an
internal sensor.
CONSTANT CJC : Use the constant value set
by users.
H02 : CNST CJC TMP
This parameter appears only when “CONSTANT CJC”
is selected for H01. Enter designated temperature value
used for CJC function. This value is a constant and not
incremented.