8. MAINTENANCE

The product starts running immediately when the power is turned on;
however, it needs 10 to 15 minutes of warm-up before it meets the
specified performance.

8.1

Calibration Apparatus

A DC voltage/current standard (Yokogawa 7651 or the equivalent)

A digital multimeter (Yokogawa 7561 or the equivalent)

A calibrator (Yokogawa M&C CA71 or the equivalent)

A precision resistor of 250

±

0.01%, 1 W

Setting tool for adjustment (Refer to “4.2 Connector for Communi-
cation” in this manual.)

8.2

Calibration Procedure

(1) Connect the instruments as shown below.
(2) Use the DC voltage/current standard and apply input signals

equivalent to 0, 25, 50, 75, and 100% of input span to the comput-
ing unit.

(3) Check to see the output values obtained from the computation of

each input are within the specified accuracy rating. “R” is used for
current output.

Use the setting tool (VJ77 Parameters Setting Tool or JHT200
Handy Terminal) or the switches on the front panel (selection
switch and adjustment switch) to adjust the input/output signals.

Input Adjustment Procedure
(1) Input the value equivalent to 0% value of input range.
(2) Call the display item (A: DISPLAY1) to check the input value in

A01: INPUT1.

(3) If the adjustment is necessary, call the adjustment item (P: AD-

JUST).

(4) Select P08: IN1 ZERO ADJ to enter the adjustment mode. Select

EXECUTE (adjustment) for adjustment. (If RESET is selected,
the adjusted value is reset to the factory-set default.)

(5) Input the value equivalent to 100% value of input range.
(6) Call the display item (A: DISPLAY1) to check the input value in

A01: INPUT1.

(7) If the adjustment is necessary, call the adjustment item (P: AD-

JUST).

(8) Select P09: IN1 SPAN ADJ to enter the adjustment mode. Select

EXECUTE (adjustment) for adjustment. (If RESET is selected,
the adjusted value is reset to the factory-set default.)

Output Adjustment Procedure
(1) When adjusting 0% value of output, call the adjustment item (P:

ADJUST) to select P26: OUT1ZERO ADJ.

(2) If there is a positive deviation, correct it by setting a negative

value to offset the deviation. If there is a negative deviation, cor-
rect it by setting a positive value.

*:

The 100% value of output can be adjusted by the same operation
as the above.
For adjustment using a setting tool, refer to the User’s Manual for
each setting tool and “7. List of Parameters” in this manual.
For adjustment using the switches on the front panel, refer to “4.3
Selection Switch and Adjustment Switch.”
User’s Manual for VJ77 [Document No.: IM 77J01J77-01E]; how-
ever, use the VJ77 of version R1.04 or later.
User’s Manual for JHT200 [Document No.: IM JF81-02E]

10 11

1

2

3

9

8

7

6

5

4

Power supply

Output

R

Ϫ

ϩ

DMM

Ϫ

ϩ

Contact input

Contact output

Ϫ

ϩ

Calibrator

Receiving resistor
( for current input)

L+

N–

GND

R: Receiving resistor
for current input

R: 250

precision resistor

for current output

R

Input

Ϫ

ϩ

DC voltge/
current
standard

9

7

8

1

2

3

4

11

5

6

10