1. Replace.

2. Replace.
3. Replace
4. Braze joint if joint is exposed where

leak has occurred.

1. Repair or replace thermostatic air vent.
2. Clean coil and fi ns. Check fi lter and
clean.

1. Check circulation pump. Check for

blocked

tubes.

2. Check voltage and correct. Check for

linted coil and clean. Check for

defective overload and repair or replace

motor.

3. On single phase motor replace motor.

On three phase motor, reverse two

leads to change rotation.

1. Change fan blade.

2. Clean fan blade.

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

Table 20 - Troubleshooting Guide

1. Frozen

coil.

2. Defective

coil.

3. Corrosion.
4. Leak in joint.

1. Check for air in coil.
2. Lint on coil fi ns.

1. No circulation of water through coil.

2. Short cycling of motor.

3. Backward rotating motor.

1. Damaged fan blade.

2. Dirty fan blade.

A. Leaking coil.

B. Poor output on steam.

C. Poor output on steam

or hot water.

D. Noisy or vibrating unit.