Ventilation air, Supply piping, Condensate piping – Mammoth V-Cube Slim Split F-Series Sizes 830 and 840 User Manual
Page 11
Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 11
Figure 12: Clearances - Units Without Waterside Economizer
SERVICE CLEARANCE
FILTER ACCESS
FILTER ACCESS
36.0 [914]
42.0 [1067]
36
.0
[9
14
]
SERVICE CLEARANCE
SERVICE CLEARANCE
Ductwork and Attenuation
Discharge ductwork is normally used with the V-Cube
Slim™. Return air ductwork may also be required.
All ductwork should conform to industry standards of
good practice as described in the ASHRAE Systems
Guide.
The discharge duct system will normally consist of a flex-
ible connector at the unit connection, a transition piece
to the full duct size, a short run of duct, and elbow with
vanes, and a trunk duct teeing into a branch duct with
discharge diffuses. The transition piece must not have
angles totaling more than 30° or severe reduction in air-
flow performance can result.
Do not connect the full duct size to the unit. Use a transi-
tion piece sized according to the discharge collar on the
unit to get to the full duct size. With metal duct material,
the sides of the elbow and entire branch duct should be
internally lined with acoustic fibrous insulation for sound
attenuation. Glass fiber duct board material is more
absorbing and may permit omission of the canvas con-
nector.
Return air ductwork (if used) should be connected to the
unit using the filter section flange.
Ventilation Air
Outside air may be required for ventilation. Refer to local
codes. The temperature of the ventilation air must be
controlled so that the mixture of outside air and return
air entering the unit is within application limits. It is rec-
ommended that the ventilation air inlet be closed during
unoccupied periods (i.e. night setback).
The ventilation air system is typically a separate building
subsystem with distribution ductwork. Simple introduction
of the outside air into each return air plenum chamber
reasonably close to the unit air inlet is recommended.
Do not duct outside air directly to the unit inlet. Provide
sufficient distance for the thorough mixing of outside and
return air.
Supply Piping
NOTE: Read all Supply Piping instructions before proceeding.
All units should be connected to supply and return piping
in a two-pipe, reverse-return configuration. A reverse-
return system is inherently self-balancing and requires
only trim balancing where multiple quantities of heat
pumps with different flow and pressure drop charac-
teristics exist in the same loop. Check for proper water
balance by measuring differential temperature reading
across the water connections.
Avoid dissimilar metal fittings as they may corrode. If the
use of dissimilar metals cannot be avoided, use dielectric
isolation at that connection point
Supply and return shutoff valves are recommended at
each unit. A flow control device to limit fluid flow through
the unit should be connected to the water outlet.
No unit should be connected to the supply and return pip-
ing until the water system has been cleaned and flushed
completely. After the cleaning and flushing has taken
place, the initial connection should have all valves wide
open in preparation for the water system flushing.
Condensate Piping
Condensate piping can be steel, copper, or PVC. Each
unit includes a minimum of two stainless steel conden-
sate connections; one in each coil cabinet section.
The condensate disposal piping must be trapped. The
piping must be pitched away from the heat pump not less
than ¼” per foot. The unit is supplied with a 1-¼” male