Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 15

Control Settings

Verify that all control jumper positions, time delay

relay settings, baud rates and control temperatures

and/or pressure settings match those indicated on

the electrical wiring diagram, as applicable. Refer to

the wiring schematics provided with your unit for loca-

tions and settings.

Verify that high and low static pressure safety settings

match those indicated on the electrical wiring diagram.

They are typically set at 3.5 inches w.c. each. Record the

values on the Startup Report form.

Refrigerant Piping

Mammoth V-Cube Slim units with DX cooling are shipped

fully charged with refrigerant from the factory. No piping

connections are needed and no field charging is required

prior to operation of the system. Check the following prior

to startup:

Verify that all pressure lines are free from the com-

pressors – i.e., not contacting or rubbing against

them – to prevent damage from vibration and friction.

Pressure line coils should have a distance between

each coil of at least one inch.

Verify that all pipe clamps have the rubber lining

intact and are secure.

Verify that all compressor service valves are open.

Startup: Power On

With the main power control panel door closed, switch on

the main power to the unit. Then carry out the following

procedures.

WARNING! Electric shock and moving equip-

ment hazard. Can cause severe injury or

death. Use extreme caution when inspecting

or servicing equipment with electrical power

supplied to the unit. Per OSHA 29 CFR

1910.333 (c)(2): “Only qualified persons may

work on electric circuit parts or equipment

that have not been de-energized. Such per-

sons shall be capable of working safely on

energized circuits and shall be familiar with

the proper use of special precautionary tech-

niques, personal protective equipment, insu-

lating and shielding materials, and insulated

tools.”

Electrical
Supply Power

Verify that the measured supply voltage matches the

rated voltage on the unit nameplate. The nameplate

is located on the electrical panel door. Record volt-

ages on the startup form.

Motor Rotation

Verify that all fans, blowers and pumps are rotating

in the correct direction. This can be accomplished

by shutting off the motors individually, using each

motor’s overload protector shut-off switch, then

observing the direction of rotation as you start them

back up.

Check for proper rotation of each compressor using

a phase rotation meter. Also verify that the unit phase

monitor is set correctly as indicated on the electrical

wiring diagram provided with your unit.