Cleaning Procedure
1. Shut down the unit by closing the main disconnect at
the power inlet.
2. Open panels or doors to gain access to both sides of
the coil section.
3. Remove soft debris from both sides of the coil with a
soft brush.
4. Using a steam cleaning machine, clean the leaving
air side of the coil first (going downward) then clean
the entering air side. Use a block-off to prevent the
steam from penetrating a dry section of the unit.
5. Allow the unit to dry thoroughly before restoring
power.
6. Damaged coil fins should be straightened by using a
fin comb.
7. Close all panels and doors once the coil is dry.
8. Restore electrical power to the unit.