Electric Models Only

All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting
wires must be properly sized to handle the rated current.

Warning (Gas Models Only)

Dryers built for use with a voltage between 200
and 240 must verify the input voltage during

!

TERM

LINE VOLTAGE

50 Hz

60 Hz

HIGH

260
226

283
249

MED

239
208

260
230

LOW

217
189

236
208

ELECTRICAL SERVICE SPECIFICATIONS

IMPORTANT:

NOTES: A.

B.

C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify
exact voltage.

When fuses are used they must be dual element, time delay, current limiting,

class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying
either local and/or National Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw rating
and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

OVEN

kW

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

M31SL

200

2

12.5

68.4

67.7

90

208

2

7.9

43.8

60

208

2

13.5

70.7

90

230

2

8.3

41.3

60

230

2

12.4

59.1

80

240

2

9.0

42.7

60

240

2

13.5

61.5

80

208

3

13.5

43.3

60

220

3

11.3

35.3

50

230

3

12.4

36.5

50

240

3

13.5

37.7

50

380

4

11.3

22.8

22.6

40

400

4

12.4

23.1

40

416

4

13.5

23.7

40

M50SL

200

2

14.8

82.1

110

208

2

16.0

85.1

110

220

2

13.4

68.8

69.4

90

230

2

14.7

72.3

100

240

2

16.0

74.2

75.1

100

200

3

14.8

51.0

70

208

3

16.0

52.6

70

220

3

13.4

43.0

43.6

60

230

3

14.7

45.3

60

240

3

16.0

46.0

60

380

4

13.4

28.0

28.6

40

400

4

14.8

29.8

40

416

4

16.0

30.7

40

M50SL Dual Voltage 480 / 120

120

2

0.0

13.2

15

480

3

16.0

19.2

25

M50SL Dual Voltage 480 / 240

240

2

0.0

6.5

15

480

3

16.0

19.2

25

M50SL Dual Voltage 600 / 120

120

2

0.0

13.2

15

600

3

16.0

15.4

20

M50SL Dual Voltage 600 / 240

240

2

0.0

6.5

15

600

3

16.0

15.4

20

M75SL

200

2

20.3

109.8

150

208

2

22.0

113.9

150

220

2

18.5

91.7

92.3

125

230

2

20.3

96.3

125

240

2

22.0

99.2

125

208

3

22.0

69.2

90

220

3

18.5

56.2

56.8

80

230

3

20.3

59.1

80

240

3

22.0

60.4

80

380

4

18.5

35.6

45

380

4

18.5

36.2

50

400

4

20.3

37.8

50

416

4

22.0

39.1

50

6/4/08

installation. If the nominal voltage
is outside of the medium
tolerances shown on the diagram
below, adjust the autotransformer,
located near the burner assembly.
To adjust the autotransformer
wiring, place the red wire on the
appropriate tap (HIGH, MED,
LOW) of the autotransformer. For
additional wiring details, refer to the electrical diagram
located on the inside of the control panel.

Electrical Service Specifications
Gas and Steam Models Only

6/4/08

ELECTRICAL SERVICE SPECIFICATIONS

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify
exact voltage.

When fuses are used they must be dual element, time delay, current limiting,
class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying
either local and/or National Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.

For others, calculate/verify correct breaker size according to appliance amp

draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

M31SL Gas

120

2

10.3

15

200

2

8.7

8.8

15

208

2

8.4

15

220

2

8.1

8.1

15

230

2

7.4

15

240

2

7.7

7.0

15

M31SL Steam

120

2

9.3

15

208

2

6.2

6.0

15

220

2

5.6

5.5

15

230

2

5.4

15

240

2

5.1

15

M50SL Gas

120

2

15.6

20

200

2

10.5

20

208

2

10.5

20

220

2

10.0

10.7

20

230

2

10.8

20

240

2

9.7

20

M50SL Steam

120

2

14.4

20

200

2

8.2

20

208

2

8.2

20

220

2

7.8

8.4

20

230

2

8.5

20

240

2

7.6

20

M75SL Gas

120

2

15.6

20

200

2

10.5

20

208

2

10.5

20

220

2

10.0

10.7

20

230

2

10.8

20

240

2

9.7

20

M75SL Steam

120

2

14.4

20

200

2

8.2

20

208

2

8.2

20

220

2

7.8

8.4

20

230

2

8.5

20

240

2

7.6

20