Operation – KROHNE OPTIWAVE 5200 FOUNDATION FIELDBUS User Manual

Page 48

Advertising
background image

4

OPERATION

48

OPTIWAVE 5200 C

www.krohne.com

09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en

UNITS_INDEX

Units Index

RW

Device Description units code index for the engineering unit

descriptor for the associated block value.

m

Settings:

m; cm; mm; ft; in; yd

DECIMAL

Decimal

R

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

SECONDARY_VALUE

SECONDARY_VALUE

SECONDARY_VALUE

SECONDARY_VALUE

electronic temperature

electronic temperature

electronic temperature

electronic temperature

The Electronic temperature.

STATUS

Status

R

Digital transducers, unlike their analog versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

-0

VALUE

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

SECONDARY_VALUE_UNIT

SECONDARY_VALUE_UNIT

SECONDARY_VALUE_UNIT

SECONDARY_VALUE_UNIT

electronic temperature unit

electronic temperature unit

electronic temperature unit

electronic temperature unit

RW

The engineering units to be used with SECONDARY_VALUE

(electronic temperature).

°C

Setting: °C

SENSOR_CAL_DATE

SENSOR_CAL_DATE

SENSOR_CAL_DATE

SENSOR_CAL_DATE

Sensor Calibration Date

Sensor Calibration Date

Sensor Calibration Date

Sensor Calibration Date

R

The date of the last sensor calibration.

-

SENSOR_CAL_LOC

SENSOR_CAL_LOC

SENSOR_CAL_LOC

SENSOR_CAL_LOC

Sensor Calibration Location

Sensor Calibration Location

Sensor Calibration Location

Sensor Calibration Location

R

The last physical location at which the sensor was calibrated.

(ex. Acme Labs)

-

SENSOR_CAL_METHOD

SENSOR_CAL_METHOD

SENSOR_CAL_METHOD

SENSOR_CAL_METHOD

Sensor Calibration method

Sensor Calibration method

Sensor Calibration method

Sensor Calibration method

R

The method of last sensor calibration. It could be one of the

several standard calibration methods defined by ISO or some

other method.

factory trim

standard

calibration

SENSOR_RANGE

SENSOR_RANGE

SENSOR_RANGE

SENSOR_RANGE

Sensor Range

Sensor Range

Sensor Range

Sensor Range

The High and Low range limit values, the engineering units

code and the number of digits to the right of the decimal point

for the sensor.

EU_100

max value

R

The engineering unit value which represents the upper end of

range of the associated block parameter.

EU_0

min value

R

The engineering unit value which represents the lower end of

range of the associated block parameter.

UNITS_INDEX

Units Index

R

Device Description units code index for the engineering unit

descriptor for the associated block value.

DECIMAL

Decimal

R

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

2

SENSOR_SN

SENSOR_SN

SENSOR_SN

SENSOR_SN

Sensor Serial Number

Sensor Serial Number

Sensor Serial Number

Sensor Serial Number

R

The sensor serial number.

SENSOR_TYPE

Sensor Type

R

The type of sensor.

Level

SENSOR_CAL_WHO

SENSOR_CAL_WHO

SENSOR_CAL_WHO

SENSOR_CAL_WHO

Sensor Calibration Who

Sensor Calibration Who

Sensor Calibration Who

Sensor Calibration Who

R

The name of the person responsible for the last sensor

calibration.

TANK_HEIGHT

TANK_HEIGHT

TANK_HEIGHT

TANK_HEIGHT

Tank Height

Tank Height

Tank Height

Tank Height

RW

The distance from the tank connecting flange face/thread stop

down to the tank bottom.

Setting:

0…100000 mm

TANK_TYPE

TANK_TYPE

TANK_TYPE

TANK_TYPE

Tank type

Tank type

Tank type

Tank type

RW

The conditions in which the device is used. If the surface of the

product is flat, select "Storage". If the surface of the product is

disturbed, select "Process". If the surface of the product is

agitated with vortexes and foam, select "Agitator".

Setting:

Storage / Process / Agitator

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value