Specification – KYORITSU 3323A User Manual

Page 6

Advertising
background image

¡

Applicable standards
IEC 61557

IEC 61010-1 Measurement CAT.III 600V Pollution degree2

Protection class II

Location for use: altitude 2000m or less

IEC 61010-031
IEC 60529

IP40

¡

Measuring range and accuracy
<Insulation resistance range>

MODEL3321A

* Heavy-line circular arc on the scale indicates the primary effective

measuring ranges. (guaranteed accuracy range)

MODEL3322A

* Heavy-line circular arc on the scale indicates the primary effective

measuring ranges. (guaranteed accuracy range)

― 4 ―

3.Specification

Nominal voltage
Max. effective scale value
Mid-scale value
Accuracy in primary
effective measuring ranges
Accuracy in primary
effective measuring ranges
Accuracy at 0 and ∞
Accuracy at no-load
voltage
Nominal current
Short-circuit current

250V

50MΩ

1MΩ

0.05∼20MΩ

within ±5% of indicated value

Measuring ranges other than above, 0 and ∞.

within ±10% of indicated value

within ±0.7% of scale length

0%∼+20% of nominal voltage

1mA 0%∼+20%

within 1.5mA

500V

100MΩ

2MΩ

0.1∼5MΩ

1000V

2000MΩ

50MΩ

2∼1000MΩ

Nominal voltage
Max. effective scale value
Mid-scale value
Accuracy in primary
effective measuring ranges
Accuracy in primary
effective measuring ranges
Accuracy at 0 and ∞
Accuracy at no-load
voltage
Nominal current
Short-circuit current

125V

20MΩ

0.5MΩ

0.02∼10MΩ

within ±5% of indicated value

Measuring ranges other than above, 0 and ∞.

within ±10% of indicated value

within ±0.7% of scale length

0%∼+20% of nominal voltage

1mA 0%∼+20%

within 1.5mA

250V

50MΩ

1MΩ

0.05∼20MΩ

500V

100MΩ

2MΩ

0.1∼50MΩ

Advertising