NSi Industries ELC74 User Manual

Page 3

Advertising
background image

1

TORK MODEL

ELC74 FOUR CHANNEL

ENERGY AND LIGHTING CONTROL

READ INSTRUCTIONS CAREFULLY BEFORE

ATTEMPTING TO INSTALL TIME SWITCH. SEE

WARNING ON FRONT PANEL – Failure to comply with

instructions could result in personal injury and/or property

damage .

INSTALLATION:

UNIT IS TO BE INSTALLED BY A LICENSED ELECTRICIAN

1 . To access mounting holes and terminal blocks, open

enclosure door (hinge on left) and internal circuit

board mounting plate (hinge on right .)

2 . Mount the enclosure at eye level using screws

or other suitable fastening device . Bring supply

and load wires in through bottom or side knockouts .

USE TOP KNOCKOUTS FOR LOW VOLTAGE

WIRING ONLY .

3 . Reinstall unit by reversing step #1 above and

connecting wires to units as per suggested

wiring diagrams at back of manual .

4 . Remove battery insulator . Unit should be

programmed with AC power . Do not program under

super cap back up power .

CAPABILITIES

- 7 day scheduling

- 128 set points

- Astronomic programming

- 4 Signal (duration) programs

- 4 Duty Cycle programs

- 26 Holidays

- 10 Block holidays

- 4 Inputs for switches or photo sensor

- Momentary output

Advertising