4.5 Configuration examples
4.5.1 On-Off controller / Signaller (inverse)
ConF / Cntr:
SP.Fn
= 0set-point controller
C.Fnc
= 0signaller with one output
C.Act
= 0inverse action
(e.g. heating applications)
ConF / Out.1:
O.Act
= 0action Out.1 direct
Y.1
=1control output Y1 active
PArA / Cntr:
Hys.l
= 0...9999 switching difference below SP
PArA / Cntr:
Hys.H
= 0...9999 switching difference above SP
PArA / SEtP:
SP.LO
= -1999...9999 set-point limit low for Weff
SP.Hi
= -1999...9999 set-point limit high for Weff
g
For direct signaller action, the controller action must be changed
(ConF / Cntr / C.Act = 1 )
Configuration level
KS 90-1 / KS 92-1
47
Configuration examples
InH.1
InL.1
SP.LO
SP
SP.Hi
100%
0%
SH
Out.1Â
InP.1Ê
setpoint
output
process value