ULSX‐CAL CONFIGURATION (continued) 

Step Seven 

 

Loop  Fail‐Safe:    This  feature  allows  you  to  select  the  fail‐safe  current 
output  if  the  sensor  fails  to  detect  a  return  signal.  When  the  sensor 
regains signal, the output current will revert back to the current level 
condition.   

o

Hold  Last  Value  ‐  The  output  will  remain  in  the  same  state  as 
the last echo detected. Example: If the output was 6.7 mA just 
prior  to  the  lost  signal,  the  device  will  continue  to  output  6.7 
mA.  Sensor will indicate the level when signal was regain. 

o

Empty  ‐  The  output  will  revert  to  the  current  value  for  an 
empty  condition.    When  “4  mA  at  Bottom”  is  selected,  the 
sensor  will  output  4  mA  when  a  fail‐safe  condition  occurs.    If 
“20  mA  at  Bottom”  is  selected,  the  sensor  will  output  20  mA 
when a fail‐safe condition occurs. 

o

Full  ‐  The  output  will  revert  to  the  current  value  for  a  full 
condition.  When “4 mA at Bottom” is selected, the sensor will 
output  20  mA  when a fail‐safe  condition  occurs.    If  “20  mA  at 
Bottom”
  is  selected,  the  sensor  will  output  4  mA  when  a  fail‐
safe condition occurs. 

o

Overfill (21 mA) ‐ The output current will go to 21 mA when the 
return signal is lost. 

o

Overfill (22 mA) ‐ The output current will go to 22 mA when the 
return signal is lost. 

Output at Empty:  This feature allows you to select the orientation of 
the  4  to  20  mA  output  (4  to  20  mA  or  20  to  4  mA).    Choose  which 
output  setting  best  fits  the  application.    Typical  installations  are  set 
with  4  mA  at  Bottom.    This  will  not  affect  the  performance  of  the 
sensor  other  than  the  output  of  the  Series  ULS.    ULSX‐CAL’s  factory 
default  is  4  mA  at  bottom  and  20  mA  at  top.  When  connecting  your 
sensor to a display, you must account for your output settings. 

o

4  mA  at  Bottom  ‐  The  output  current  will  be  4  mA  when  the 
sensor  measures  an  empty  tank  and  20  mA  when  the  sensor 
measures a full tank.   

o

20 mA at Bottom ‐ The output current will be 20 mA when the 
sensor  measures  an  empty  tank  and  4  mA  when  the  sensor 
measures a full tank. 

Note: Right click on any menu that you may have questions on to open the help menu. 

Note: To reset, press the Clear Screen button. 
 
 

 