ULSX‐CAL TANK LEVELS / WRITE TO UNIT 

Step Seven 

ULSX‐CAL ‐ Tank Levels:  This section of ULSX‐CAL is where you enter application measurement values.  This 
applies to all versions of the Series ULS.  You must enter the Sensor Height and Fill Height values.   

 For  the  Series  ULSS,  ULSM  and  ULSL,  the  Sensor  Height  and  Fill  Height  values  determine  the 

operational range for the 4‐20 mA output.   

 

 

Sensor Height: Distance from 
the bottom of the tank to the 
bottom of the transducer.    
 
Fill Height: Distance from the 
bottom of the tank to the 
maximum liquid height. 

 

ULSX‐CAL ‐ Relay Values:  (Series ULSS, ULSM and ULSL only):  This section of ULSX‐CAL is where you enter 
the operational values for relays.  You must enter values within all of the fields shown.  The value fields shown 
are  based  upon  the  configuration  of  the  Series  ULS.    All  values  must  be  in  the  units  of  operation  selected 
above and are based upon units of liquid.  All relay values must be greater than Liquid Empty (0) and less than 
Liquid Full (Fill Height).     

 

Example: This sample shows 4 
High  Level  Alarms.    As  the 
level  increases  from  the 
bottom  –up,  each  alarm  will 
activate at 4” increments.  

Example: This sample shows a 
2‐Pump  Lead/Lag  operation 
with  a  High  and  Low  alarm.  
The  pumps  will  automatically 
empty  the  tank  and  the 
alarms will activate if the level 
gets too high or low.  

 

 

 