8. PID auto-tuning of the SCZ10

In order to decide each P, I, D value and ARW automatically, this system gives a fluctuation

to the controlled object to get a optimal value.

3 types of fluctuation below are automatically selected.

[ When the difference between setting value and processing temperature is large in rising]

When AT bias is set to 20°C(°F)), a fluctuation is given at the temperature 20°C(°F

[When control is stable]

A fluctuation is given at the setting value.

[ When the difference between the setting value and processing temperature is large when

temperature falls]

When AT bias is set to 20°C(°F), a fluctuation is given at the temperature 20°C(°F)

(

higher than the

Setting

value

Temp.

Time

AT

(1)

(2)

(3)

Temperature 20

°C(°F)

lower

than the setting value

(4)

:

AT

Auto-tuning starting point

Calculating PID constant

PID contatnt calculated
Controlled by the PID
constant set by auto-tuning.
AT bias setting value

(1):
(2):

(3):

(4):

Temp.

Time

AT

(1)

(2)

(3)

:

AT

Auto-tuning starting point

Setting

value

Calculating PID constant

PID constant calculated

Controlled by PID constant
set by auto-tuning

(3):

(2):

(1):

Setting

value

Temp.

Time

AT

(1)

(2)

(3)

:

AT

Auto-tuning starting point

(1): Calculating PID constacnt
(2): PID constant calculated
(3): Controlled by PID constant

set by auto-tuning

(4): AT bias setting value

(4)

Temperature 20

°C(°F)

higher

than the setting value