Factory default procedure, Menu selections, Primary menu – Dwyer 32DZ User Manual

Page 14

Advertising
background image

949-1318

Page 14 of 40

June, 2000

FACTORY DEFAULT PROCEDURE

If for any reason you wish to restore the factory settings use the following
procedure.
1.

Turn off power to control

2.

Turn on power to control

3.

While control is performing

SELF

SELF

SELF

SELF

SELF

tESt

tESt

tESt

tESt

tESt

, press and hold the

INDEX

and

ENTER keys.

4.

The control will display the ROM ID code. Press

INDEX.

5.

The control will display

FACt

FACt

FACt

FACt

FACt

dFLt

dFLt

dFLt

dFLt

dFLt

. If you wish to just restore factory

settings, Press

ENTER and

DOWN ARROW at the same

time. The control will be reset to the original factory settings.

6.

Press

INDEX to display

OPt

OPt

OPt

OPt

OPt

. If your control is equipped with an

option, press the UP ARROW to display the option number. If the
number is flashing, press

ENTER. An enabled option does not

flash.

7. Press

INDEX to display

ACPt

ACPt

ACPt

ACPt

ACPt

. Select

YES

YES

YES

YES

YES

or

no

no

no

no

no

.

YES

YES

YES

YES

YES

Changes are accepted and control re-boots.

no

no

no

no

no

Changes are discarded and control re-boots.

8. Press

ENTER.

The control will re-initialize with Factory Default settings.

THE BAUD RATE AND ADDRESS MENU ITEMS WILL TAKE EFFECT ON THE
NEXT POWER UP OF THE CONTROL. BE SURE TO POWER CYCLE THE
CONTROL BEFORE USING THE NEW BAUD RATE AND ADDRESS.

In operation, you have the option of preventing a write command from the host
computer. To prevent the host from writing to the control change the

LOrE

LOrE

LOrE

LOrE

LOrE

menu

item in the Secondary Menu to

LOC

LOC

LOC

LOC

LOC

. To allow the host to write commands to

the control set

LOrE

LOrE

LOrE

LOrE

LOrE

to

rE

rE

rE

rE

rE

. (The host does have the ability to change the

LOrE

LOrE

LOrE

LOrE

LOrE

state, but it is not automatic.)

If your system depends on constant reading or writing to and from the host, you
may wish to set the No Activity Timer (

nAt

nAt

nAt

nAt

nAt

) to monitor the addressing of the

control. When the

LOrE

LOrE

LOrE

LOrE

LOrE

is set to

rE

rE

rE

rE

rE

and the

nAt

nAt

nAt

nAt

nAt

is set to any value other than

Off

, the control will expect to be addressed on a regular basis. If the control

is not addressed in the time set by the value of

nAt

nAt

nAt

nAt

nAt

, then the control will display

the error message

CHEC LOrE

CHEC LOrE

CHEC LOrE

CHEC LOrE

CHEC LOrE

. To clear the message set

LOrE

LOrE

LOrE

LOrE

LOrE

to

LOC

LOC

LOC

LOC

LOC

.