5.2.4

Cable glanding

All cables into the enclosures must be glanded to IP65 standards to
maintain this rating for the enclosure as a whole. Cable glands and
gland plates are not supplied. Glanding requirements vary for each
enclosure as follows:

DX070
On the DX070, 'knockout' holes are provided, in two different sizes
(15.5 mm and 21 mm), on the side faces of the base. See table 5.7 for
recommended cable glands.
Note: The enclosure may have three or four knockout holes on each
side depending on the manufacturer. Consequently, there may be a
choice of either six or eight positions for cable glands.

DX170
The DX170 can accommodate one gland plate on each side - see figure
5.10 for details. Table 5.6 lists suppliers of suitable gland plate kits and
Table 5.7 lists recommended glands.

DX430
The DX430 can accommodate two gland plates on each side - see figure
5.11 for details. Table 5.6 lists suppliers of suitable gland plate kits and
Table 5.7 lists recommended glands.

10

INM5000-6 Jul 2010

107

137

157

187

Ш 5.5

520

576

249

305

Ш 7.0

Gland plate

Typical gland

positions

Gland plate

Typical gland

positions

249

305

339

395

Ø 7.0

Figure 5.7: Dimensions and location of fixing holes - DX070

Figure 5.8: Dimensions and location of fixing holes - DX170

Figure 5.9: Dimensions and location of fixing holes - DX430

Figure 5.10: Cable gland plate locations on a DX170 enclosure

Figure 5.11: Cable gland plate locations on a DX430 enclosure