Dwyer MTL5045 User Manual

Page 18

Advertising
background image

14

INM5000-6 Jul 2010

6.4.2

Outputs

The output 1 relay reflects the status of the input and may be configured
to operate in reverse phase (PR) or with line-fault detection (LF). The
output 2 relay may be configured either to follow (slave mode) output 1
or as a line-integrity monitor (LFD) (see 6.4.3).

6.4.3

Line fault detection

(See section 3.1.4 for definition of a line fault)
Line-fault detection and the operational mode of output 2 (ie slave to
output 1 or LFD) are selected by switches located on the top of the
module (see figure 6.8).
When LFD is selected for output 2 and there is a line fault in the sensor
circuit the output 2 relay is de-energised (providing an alarm output).
When LF is selected for output 1, the output 1 relay is de-energised if
there is a line fault in the sensor circuit. Note that resistors must be fitted
when using LFD with a contact input; 500

Ω to 1kΩ in series, and 20kΩ

to 25k

Ω in parallel with the switch.

6.4.4

Testing

Make the relevant safe- and hazardous-area connections shown in figure
6.9 for the tests listed in table 6.3. (Figure 6.8 shows the switch positions
for configuring output 2 slave/LFD, output 1 line fault (LF) and phase
reversal (PR)).

Table 6.3

6.5

MTL5015 solid-state two-channel
switch/proximity detector with line
fault detection and phase reversal

The MTL5015 enables each of two safe-area loads to be controlled,
through a solid-state output, by a switch or proximity detector in a
hazardous area. Line fault detection (LFD) and output phase reversal
(see 3.1.3) facilities are included.

6.5.1

Wiring connections

See figure 6.10 for wiring connections.

Phase

Line fault

Output 1

Output 2

Status

Fault

reverse

detection

Slave

Input test switch position

relay

relay

LED

LED

Test

switch (PR)

(LF)

(LFD)

(terminals 1 & 2)

(11-12)

(9-8)

(yellow)

(red)

1

Normal

Off

LFD

(a) i.e. short-circuit

Closed

Open

On

On

2

Reverse

Off

LFD

(a) short-circuit (I

sc

=7–9mA)

Open

Open

Off

On

3

Normal

On

Slave

(a) short-circuit

Open

Open

Off

On

4

Normal

Off

Slave

(a) short-circuit

Closed

Closed

On

Off

5

Normal

Off

Slave

open-circuit (V

oc

=7V5–9V5)

Open

Open

Off

Off

6

Normal

On

Slave

open-circuit

Open

Open

Off

On

7

Normal

Off

LFD

(b) 22k

Ω

Open

Closed

Off

Off

8

Normal

Off

LFD

(c) 680

Ω

Closed

Closed

On

Off

LF
PR

O/P1

ON

SLAVE LFD

Output 2

MTL5014

PWR

Ou

tpu

t 1 f

oll

ow

s

sensor

Ou

tpu

t 2

slav

es

o

ut

pu

t 1

Ou

tpu

t 1 f

oll

ow

s

sensor

Ou

tpu

t 2 m

on

itors

LFD

Ou

tpu

t 1 f

oll

ow

s

sensor

& LFD

Ou

tpu

t 2

slav

es

o

ut

pu

t 1

Ou

tpu

t 1 f

oll

ow

s

sensor

& LFD

Ou

tpu

t 2 m

on

itors

LFD

Ou

tpu

t 1 i

n pha

se

wi

th

sensor

Ou

tpu

t 1 i

n a

nt

i-pha

se

wi

th

sensor

(LFD

not

aff

ecte

d)

6

5

4
3

2

1

7

8

9

10

11

12

13

14

Vs–

Vs+

20 to 35V dc

Output 2

relay

Output 1

relay

To earth

leakage

detector

SW

22kW

680W

a

b

c

+

–

open

Terminal

Function

1

Input –ve (Ch 1)

2

Input +ve (Ch 1)

3

Earth leakage detection

4

Input –ve (Ch 2)

5

Input +ve (Ch 2)

6

Earth leakage detection

8

Output –ve (Ch 2)

9

Output +ve (Ch 2)

11

Output –ve (Ch 1)

12

Output +ve (Ch 1)

13

Supply –ve

14

Supply +ve

6

5

4
3

2

1

7

8

9

10

11

12

13

14

To earth leakage

detector

SW

22kW

680W

a

b

c

open

22kW

+

–

Vs–

Vs+

20 to 35V dc

} V

d2

1kW

1kW

+

–

+

–

} V

d1

Ch1

Ch2

+

–

Figure 6.8: Top label of MTL5014 with explanation of switch positions

Figure 6.9: Test circuit for MTL:5014

Figure 6.11: Test circuit for MTL5015

6

5

4
3

2

1

7

8

9

10

11

12

13

14

Vs–

Vs+

20 to 35V dc

To earth

leakage

detector

22kW

680W

+

–

Resistors required only

for line fault detection

Ch 2

22kW

680W

+

–

Ch 1

+

–

+

–

Figure 6.10: MTL5015 wiring diagram and connections

Hazardous area

Safe area

Advertising
This manual is related to the following products: