Alarms and events, 0 alarms and events – APC SILCON 60-80KW 208/480V UPS User Manual
Page 24
24
User Guide APC Silcon 60-80kW 208V/480V UPS
990-4035
Alarms and Events
5.0 Alarms and Events
Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30
seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and
if more in the same order as they arise.
Certain alarms, such as battery alarms, need resetting. See section 4.0 Parameter Settings.
All alarms are also registered in an event logger and remains there in a stack with room for
250 events. The events are stored in the same order as they arose - showing the latest first.
Besides the alarms the following operational modes are also stored in the event logger.
Mode
Comments
MPU is reset
UPS has been completely switched off
Stand-by
UPS has been in stand-by mode by parallel system
Normal operation
UPS has been in normal operation
Battery operation
UPS has been in battery operation
Bypass operation
UPS has been in bypass operation
System off
UPS has been off
5.1
Displaying the Alarm Stack
5.2
Displaying the Event Stack
Action
Description
1. Press
Access to the alarm stack.
2. Press
or
Scroll up or down through the alarm stack
messages.
Last message is "No (further) alarm".
3. Press
Exits the alarm stack. If not operated the system
will exit the alarm stack automatically after 30
seconds.
Action
Description
1. Press
and
Press the two keys simultaneously to get access
to the events stack
2. Press
or
Scroll up or down through the event stack
(last message is "No (further) event").
3. Press
Displays the time where the event happened.
4. Press
Exits the event stack. If not operated the system
will exit the event stack automatically after 30
seconds.