Alarms and events, 0 alarms and events – APC SILCON 60-80KW 208/480V UPS User Manual

Page 24

Advertising
background image

24

User Guide APC Silcon 60-80kW 208V/480V UPS

990-4035

Alarms and Events

5.0 Alarms and Events

Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30
seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and
if more in the same order as they arise.

Certain alarms, such as battery alarms, need resetting. See section 4.0 Parameter Settings.

All alarms are also registered in an event logger and remains there in a stack with room for
250 events. The events are stored in the same order as they arose - showing the latest first.

Besides the alarms the following operational modes are also stored in the event logger.

Mode

Comments

MPU is reset

UPS has been completely switched off

Stand-by

UPS has been in stand-by mode by parallel system

Normal operation

UPS has been in normal operation

Battery operation

UPS has been in battery operation

Bypass operation

UPS has been in bypass operation

System off

UPS has been off

5.1

Displaying the Alarm Stack

5.2

Displaying the Event Stack

Action

Description

1. Press

Access to the alarm stack.

2. Press

or

Scroll up or down through the alarm stack
messages.
Last message is "No (further) alarm".

3. Press

Exits the alarm stack. If not operated the system
will exit the alarm stack automatically after 30
seconds.

Action

Description

1. Press

and

Press the two keys simultaneously to get access
to the events stack

2. Press

or

Scroll up or down through the event stack
(last message is "No (further) event").

3. Press

Displays the time where the event happened.

4. Press

Exits the event stack. If not operated the system
will exit the event stack automatically after 30
seconds.