Alarms and events – APC SILCON 60-80KW 208/480V UPS User Manual
Page 25
Alarms and Events
990-4035
User Guide APC Silcon 60-80kW 208V/480V UPS
25
5.3
Possible Alarms
NOTICE!
Please note mains = utility
Alarms
Description
Action
1. Peak current limiter active
Peak current limiter activated and
UPS switched to bypass
operation.
System overload
Check for blown fuses in
installation
2. Bypass power supply fault
Fault in redundant PSU for
bypass. UPS still 100% able to
operate in all modes.
Call for assistance
3. Delta current limiter active
Input current limiter activated and
UPS switched to bypass
operation
Check for overload.
If message is repetitive -
call for assistance
4. Faulty fan
Blocked or faulty fan
Remove blocking or replace fan
5. High DC warning
Switching off big output load
If alarm is repeated, reduce load
change
6. High DC shutdown
UPS fault
Call for assistance
7. Off-button activated
Off button or emergency power
shut down activated
–
8. Synchronization error
UPS unable to synchronize with
input frequency
Check if phase rotation of mains
input voltage is correct. If OK, call
for assistance
9. Inverter voltage error
Inverter average voltage outside
limits (normal message during
system start-up/switch-off
–
10. Parallel synchronization
error
Parallel UPS unable to
synchronize
Check external parallel cables -
call for assistance
11. Inverter current limiter active
Inverter overload
Reduce UPS output load
12. Overload. Load exceeding
100%
UPS overload
Reduce UPS output load
13. Second power supply fault
UPS fault
(only systems > 160kW)
Call for assistance
14. Internal power supply fault
UPS fault. Only bypass operation
possible
Call for assistance
15. Battery MCCB is off
Battery MCCB/fuse not closed or
released
Close MCCB / insert new fuse. If
released again -
call for assistance.
16. **Q004 off**
Output switch position for UPS in
parallel
–
17. **Q003 off**
External bypass switch position
–
18. **Q002 off**
UPS output switch position
–