Troubleshooting, Table 6 troubleshooting – Outback Power Systems GS4048A Operators Manual User Manual

Page 55

Advertising
background image

Troubleshooting

900-0161-01-00 Rev A

53

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

Loads sensitive to inverter’s
transfer time.

UPS mode not in

use on the appropriate input.

MATE3 system display only: Most of the inverter’s input modes
feature a small but noticeable response time during transfer.

Certain loads (such as highly sensitive computers) may not

respond well. The

UPS input mode has a faster response time.

Select this mode for the appropriate input. (See page 17.)

Loads too large.

The unit can transfer more power than it can invert. If loads are

oversized, the unit will falter or crash when switching to batteries.

Reduce the size of the loads.

Undersized battery cables.

Battery cables smaller than recommended will cause a significant

voltage drop when switching to batteries, acting like either an

overload or a low-battery condition. Size all cables correctly.

Unit reads AC input,

even though no

source is present.

Internal transfer relay may be

damaged. May be

accompanied by

AC Relay Fault

error and shutdown.

Disconnect AC input wires and turn inverter on. Test the AC input

and neutral test points with an AC voltmeter. (See page 49.) If

voltage appears there, the transfer relay may be jammed. Contact
OutBack Technical Support.

5

This problem is not common. If this

occurs, it is usually on only the Grid or Gen input — not both.

False reading due to noise.

Electrical noise can cause false readings on the metering circuits
when no voltage is present. The readings are usually less than

30 Vac. If this is the case, no action is required.

Inverter clicks
repeatedly. AC

output voltage rises

or drops to unusual

levels with every

click.

Inverter’s output has been

connected to its input. Voltage
shifts are the result of trying to

match its own voltage.

Disconnect the wires from the inverter’s AC input or AC output

terminals, or both. If the problem immediately disappears, it is an
external wiring issue. The inverter’s

AC IN and AC OUT must

remain isolated from each other.

Low AC input voltage. Can be
caused by weak AC source, or

by faulty input connection.

Test AC hot and neutral input test points with an AC voltmeter.
(See page 49.) If low or fluctuating, this is an external problem.

A generator is connected to the
input terminals while the unit is
in the

Grid Tied input mode.

The inverter is not intended to sell power to a generator. The
selling activity will drive the generator voltage up to the

disconnection point. It will then reconnect to the generator and

try again. Change input modes, or move the generator to an

input with a different mode selected.

Inverter hums

loudly. System

display may show

messages for high
battery voltage,

low battery voltage,

or backfeed error.

Inverter output is being fed

with an external AC source that

is out of phase.

Disconnect AC output wires. Turn the inverter off and then on. If

the problem clears, reconnect the AC output wires. If the

problem recurs when reconnected, an external AC source is
connected to the output.

Inverter has been incorrectly
stacked with another unit on

the same output. All units

come defaulted as master.

Check HUB ports and make certain the master inverter is plugged
into port 1.
MATE3 system display only: Check stacking settings in the

Inverter

Stacking menu. Only one master is allowed per system.

5

See inside front cover of this manual.

Advertising
This manual is related to the following products: