Mechanical specifications, Environmental specifications, Specifications – Outback Power Systems GS4048A Operators Manual User Manual

Page 64

Advertising
background image

Specifications

62

900-0161-01-00 Rev A

Table 12

Electrical Specifications for Radian Models

Specification

GS8048A

GS4048A

DC Input Power (continuous)

9.5 kVA

4.8 kVA

DC Input Maximum Current (continuous full power)

200 Adc

100 Adc

DC Input Maximum Current (surge)

424.2 Adc

212.1 Adc

DC Input Maximum Current (short-circuit)

8975 Adc

4488 Adc

Battery Charger Maximum AC Input

30 Aac at 240 Vac

15 Aac at 240 Vac

Battery Charger Maximum DC Output

115 Adc

57.5 Adc

DC Output Voltage Range (charging)

44 to 68 Vdc

44 to 68 Vdc

Auxiliary Output

0.7 Adc at 12 Vdc

0.7 Adc at 12 Vdc

Auxiliary Relay

10 A at 250 Vac or 30 Vdc

10 A at 250 Vac or 30 Vdc

Mechanical Specifications

Table 13

Mechanical Specifications for Radian Models

Specification

GS8048A

GS4048A

Inverter Dimensions (H x W x D)

28 x 16 x 8.75"

(71.1 x 40.6 x 22.2 cm)

28 x 16 x 8.75"

(71.1 x 40.6 x 22.2 cm)

Shipping Dimensions (H x W x L)

14.5 x 21 x 34.5"

(36.8 x 53.3 x 87.6 cm)

14.5 x 21 x 34.5"

(36.8 x 53.3 x 87.6 cm)

Inverter Weight

125 lb (56.8 kg)

82 lb (37.2 kg)

Shipping Weight

140 lb (63.5 kg)

89 lb (40.3 kg)

Accessory Ports

RJ11 (batt temp) and RJ45

(remote)

RJ11 (batt temp) and RJ45

(remote)

Non-volatile Memory

Yes

Yes

Neutral-Ground Bond Switching

No

No

Chassis Type

Vented

Vented

Environmental Specifications

Table 14

Environmental Specifications for Radian Models

Specification

Value

Rated Temperature Range (meets component specifications; however,
please note that the inverter output wattage is derated above 25°C)

–4°F to 122°F (–20°C to 50°C)

Operational Temperature Range (functions, but not rated for operation;

does not necessarily meet all component specifications)

–40°F to 140°F (–40°C to 60°C)

Storage Temperature Range

–40°F to 140°F (–40°C to 60°C)

IP (Ingress Protection) Rating of Enclosure

IP20

Environmental Category

Indoor unconditioned

Wet Locations Classification

Wet locations: No

Relative Humidity Rating

93%

Pollution Degree Classification

PD 2

Maximum Altitude Rating

6561’ (2000 m)

Overvoltage Category (AC Input)

3

Overvoltage Category (DC Input)

1