Locating the new water heater (cont’d) – State PR6 75 XRVIT User Manual

Page 10

Advertising
background image

Combustion Air and Ventilation

for Appliances Located in

Confined Spaces

Confined Space is a space whose volume is less than 50 cubic

feet per 1,000 Btu per hour of the aggregate input rating of all

appliances installed in that space.

a. ALL AIR FROM INSIDE BUILDINGS:

(See Page 8 Figure 1, and Figure 6 below)

The confined space shall be provided with two permanent

openings communicating directly with an additional room(s)

of sufficient volume so that the combined volume of all spaces

meets the criteria for an unconfined space. The total input of

all gas utilization equipment installed in the combined space

shall be considered in making this determination. Each open-

ing shall have a minimum free area of one square inch per

1,000 BTU per hour of the total input rating of all gas utiliza-

tion equipment in the confined space, but not less than 100

square inches. One opening shall commence within 12 inch-

es of the top and one commencing within 12 inches of the

bottom of the enclosure.

b. ALL AIR FROM OUTDOORS: (see Figures 7-9)

The confined space shall be provided with two permanent

openings, one commencing within 12 inches of the top and

one commencing within 12 inches from the bottom of the

enclosure. The openings shall communicate directly, or by

ducts, with the outdoors or spaces (crawl or attic) that freely

communicate with the outdoors.

2. When communicating with the outdoors through vertical

ducts, each opening shall have a minimum free area of 1

square inch per 4,000 BTU per hour of total input rating of

all equipment in the enclosure. (See Figure 8.)

3. When communicating with the outdoors through horizon-

tal ducts, each opening shall have a minimum free area of

1 square inch per 2,000 BTU per hour of total input rating

of all equipment in the enclosure. (See Figure 9.)

4. When ducts are used, they shall be of the same cross-sec-

tional area as the free area of the openings to which they

connect. The minimum short side dimension of rectangular

air ducts shall not be less than 3 inches. (See Figure 9.)

5. Louvers and Grilles: In calculating free area, consideration

shall be given to the blocking effect of louvers, grilles or

screens protecting openings. Screens used shall not be small-

er than

1

4

inch mesh. If the free area through a design of lou-

ver or grille is known, it should be used in calculating the

size opening required to provide the free area specified. If

the design and free area is not known, it may be assumed

that wood louvers will be 20-25 percent free area and metal

louvers and grilles will have 60-75 percent free area. Louvers

and grilles shall be fixed in the open position or interlocked

with the equipment so that they are opened automatically

during equipment operation.

6. Special Conditions Created by Mechanical Exhausting or

Fireplaces: Operation of exhaust fans, ventilation systems,

clothes dryers or fireplaces may create conditions requiring

special attention to avoid unsatisfactory operation of

installed gas utilization equipment.

Locating the New Water Heater (cont’d)

Figure 6

Figure 8

Figure 9

Figure 7

10

1. When directly communicating with the outdoors, each

opening shall have a minimum free area of 1 square inch

per 4,000 BTU per hour of total input rating of all equip-

ment in the enclosure. (See Figure 6.)

OPENINGS

VENTILATION LOUVERS

(each end of attic)

VENT THROUGH

ROOF

WATER

HEATER

WATER

HEATER

VENT TO

OUTDOORS

VENT TO

OUTDOORS

INLET AIR

DUCT

VENTILATION LOUVERS

VENT THROUGH

ROOF

VENT THROUGH ROOF

VENT TO

OUTDOORS

VENT TO

OUTDOORS

VENT THROUGH

ROOF

VENTILATION LOUVERS

(each end of attic)

WATER

HEATER

AIR OUTLET

INLET AIR DUCT

(ends 1

″ above floor)

OUTLET AIR DUCT

INLET AIR DUCT

Advertising
This manual is related to the following products: