Page 41
Advertising
2. Installation
2−9
Festo P.BE−CPX−CEC−EN en 1004a
DIL switch 2
For CPX−CEC−C1/−M1, you can switch the CAN bus termination
(120 ġ) on or off.
CPX−CEC−C1/−M1
DIL switch 2
Termination switched off
DIL 2.1: OFF
DIL 2.2: OFF
Termination switched on
DIL 2.1: ON
DIL 2.2: OFF
All further switch settings are reserved.
The DIL switch 2 on the CPX−CEC has no function.
Tab. 2/3:
Setting the DIL switch 2