Network Transformer Instruction Manual

containers. Do not store the transformer in a

corrosive environment.

If the transformer is to be stored for an extended

period of time before being placed into service,

it should be stored on a firm level surface. The

gas space above the insulating fluid should be

pressurized with dry nitrogen to a pressure of 2-3

PSIG. This will prevent a negative internal pressure

that might draw moisture into the main tank, switch

chamber, or terminal chamber. Prior to storage, be

sure that the primary bushings or bushing wells

are fitted with their protective dust covers, and the

secondary throat shipping guard is installed.

The transformer should be inspected periodically

while it is in storage. Ensure that an effective

pressure seal is maintained, and check for leaks

and corrosion. Any damage or defect should be

repaired immediately.