USER OPERATION AND MAINTENANCE

HP SERIES

PORTABLE PUMPS

19

Insert the bolts and secure in place with

lockwashers and nuts provided.

4. When the pump is mounted and if

access is not provided to fill the fuel tank

install optional fill tube and vent

extension as required.

NOTE: The fuel tank on the HP
series pump is already vented,
therefore a vented fuel cap is
not required

5. Locate and install the instrument

panel on the apparatus. A dimensional

drawing is provided of the instrument

panel to locate the mounting holes.

(NOTE: Approximately 2 meters (6 feet)

of wire and control cables is provided

with the pump. When locating the

instrument panel the installer must take

this into account.) Make electrical

connection from the instrument panel to

the pump with the jumper wires

provided.

6. Connect throttle lever and choke

control to the engine. Secure in place

with the clamps provided. After the

connections are made ensure the

controls work smoothly. There may be

excess cable after the connections are

made. Make a loose coil of the cable

and secure in place with wire ties.

CAUTION: The pump and
motor assembly are vibration

isolated. When making the
permanent connections to the
suction and discharge fittings
DO NOT use hard piping. A
short length of flexible piping is
required to prevent damage
to the pump and engine.

7. Make piping connections to the

discharge flange as required. When

making the piping connections it may

be necessary to turn the pump volute

for proper alignment. To turn the pump

volute:

a. Loosen and remove the "V"-band

clamp using a 1/2 inch or 13 mm

deep well socket.

b. Remove the volute from the

pump body.

c. Locate and remove the

positioning roll pin from the pump

b o d y .

d. Return the volute to the pump

body and install "V"-band clamp.

e. Turn the volute as necessary when

V-BAND CLAMP

TIGHTENING NUT

Advertising