3 cabin controls (23x), Cabin controls (23x), Electrical system – JLG 4017RS Service Manual User Manual
Page 188

Electrical System
9-36
3614RS, 4017RS
9.13.3
Cabin Controls (23X)
Message
Fault
Code
Indicators
Other Actions Taken
Trigger for Fault
Latch Until
CONFLICTING FRAME
LEVEL SIGNALS
2322
5000Ms
Frame Level Left and Frame Level
Right are prevented
UGM J4-9 Frame Level Left and UGM
J4-17 Frame Level Right digital
inputs are energized together
Power cycled
CABIN JOYSTICK – X
AXIS FAULT
2323
Continuously
Cabin joystick X-axis is prevented
Elobau Cabin Joystick configured:
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf010:E2, 0Xf011:E2,
or 0Xf012:E2
Cabin joystick transmit 1022 as the
X-Axis position
Cabin joystick transmits Error (1:0)
for the X-Axis
Neutral, Left, or Right Position
Power cycled
CABIN JOYSTICK – Y
AXIS FAULT
2324
Continuously
Cabin joystick Y-axis is prevented
Elobau Cabin Joystick configured:
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf020:E2, 0Xf021:E2,
or 0Xf022:E2
Cabin joystick transmits 1022 as the
Y-Axis position
Cabin joystick transmits Error (1:0)
for the Y-Axis Neutral, Forward, or
Backward Position
Power cycled
CABIN JOYSTICK – UP
BUTTON FAULT
2327
Continuously
Downshift & upshift buttons are
prevented
Elobau Cabin Joystick configured:
Cabin joystick transmits Error (1:0)
for the upshift button
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf064:FF
Power cycled
CABIN JOYSTICK –
DOWN BUTTON
FAULT
2326
Continuously
Downshift & upshift buttons are
prevented
Elobau Cabin Joystick configured:
Cabin joystick transmits Error (1:0)
for the downshift button
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf065:FF
Power cycled
CABIN JOYSTICK –
AUX CONTINOUS
FAULT
2330
Continuously
AUX Continuous function requests
will be ignored by the UGM
(Continuous Auxiliary; Auxiliary
Pressure Release)
Elobau Cabin Joystick configured:
Cabin joystick transmits Error (1:0)
for the AUX Continuous Auxiliary;
Auxiliary Pressure Release) button
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf063:FF
Power cycled
HYDRAULIC FILTER
RESTRICTION
2332
5000Ms
–
Five minutes after engine start, UGM
J2-24 Hydraulic Filter Restriction
Switch digital input is grounded for
25,000Ms
UGM J2-24
Hydraulic Filter
Restriction
Switch digital
input is not
grounded for
1,000Ms
LOAD MOMENT
SHUTOFF INPUT –
INVALID SIGNAL
2336
5000Ms
Load Moment Shutoff Switch is
ignored
UGM J4-33 Load Moment Shutoff
digital input is energized at power
up or for 40 Seconds
Power cycled