Group configuration, Group trend configuration, Nanodac – Carbolite nanodac User Manual

Page 60: 2 group configuration

Advertising
background image

nanodac™

MC27 –EN– 1.04

58

= 8; Number of stop bits = 1; no flow control. Can be set to ‘Modbus Slave’ or ‘Off’.
The unit must be restarted before any change takes effect.

Time Format

Allows the user to choose milliseconds, seconds, minutes or hours as the time
format. Sets the resolution for the reading and writing of time format parameters.

PrefMaster Conn

Read only. Shows the IP address of the preferred master, when connected.

Response Time

Read only. Shows the response time for a single communications request to the
relevant master.

Master Conn 1 to 4

Read only. Shows the IP addresses of any other masters connected to this
recorder.

5.2 GROUP CONFIGURATION

Group configuration is separated into two areas, one which defines trending characteristics (for display
channels) the other defining the recording characteristics for saving data to the Flash memory ready for
archiving.

5.2.1 Group Trend configuration

This allows the user to define which points are to be traced on the display and at what interval, and also
allows the number of chart divisions to be set up. Figure 2.3.1 shows a typical configuration page.

Note: The background chart colour is set up as a part of Instrument Display configuration.

















Figure 2.3.1 Group Trend Configuration

Descriptor

Allows the user to enter a descriptor (20 characters max.) for the group.

Interval

The trending interval which defines how much data appears on one screen height
or width. A number of discrete intervals can be chosen between 0.125 seconds to 1
hour. The selection should be made according to how much detail is required, and
how much data is to be visible on the screen.

Major Divisions

Allows the user to select the number of divisions into which the scale is divided and
how many gridlines are displayed. Setting the value to 1 results in just the zero and
full scale values appearing. Setting the value to 10 (the maximum) results in a scale
with zero, full scale and nine intermediate values appearing, with associated grid
lines.

Point1 to Point6

Allows the user to select which channels and virtual channels are to be traced. The
maximum number of traces is six.

Descriptor

Interval

Major Divisions

Point1

Point2

Point3

Point4

Group.Trend

Group 1

0.25 sec

10

Channel1

Channel2

Channel3

Channel4

Point5

Point6

No Trend

VirtualChan1