Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse User Manual

Page 10

Advertising
background image

8

95-8526

14.2

optional relayS
Optional relay contacts are “dry”, meaning that the

installer must provide the voltage to the common terminal

of the relay output.

AC voltage should not be switched directly using the

Eclipse relays. The use of an external relay is required if

AC voltage must be switched by the Eclipse relays.

In order to change alarm relay settings from the factory

default settings, it is recommended to utilize a HART

Field Communicator. Contact the factory for further

assistance.

NOTE

Refer to “Alarm Relays” in the Specifications section
of this manual for important information regarding
alarm relays.

The relay board must temporarily be removed from

the Eclipse termination compartment to connect the

relay output field wiring cables. After the relay wiring

is connected, re-install the relay board using the three

captive screws. Refer to Figure 3.

wiring proCeDUre
Ensure that all cables are terminated properly. Pointwatch

Eclipse screw terminal torque range is 3.5–4.4 in.-lbs.

(0.4–0.5 N·m).

Conductor insulation should be stripped off with a bare

conductor length of 0.2 inch (5 mm) minimum and 0.7

inch (18 mm) maximum.

Cable shield, if used, should be properly terminated. If

not terminated, clip the shield wire off short and insulate

it within the detector housing to prevent the shield wire

from accidentally contacting the detector housing or any

other wire.

Figure 4 shows the wiring terminal strip located inside the

detector’s integral junction box.

Figure 5 shows the wiring terminal configuration for the

standard Eclipse without relays.

Figure 6 shows the wiring terminal configuration for the

standard Eclipse with relays.

Figures 7 through 10 show the 4-20 mA output of the

Eclipse detector in various wiring schemes.

Figure 11 shows a standard Eclipse wired to a FlexVu

UD10 Universal Display Unit.

Figure 12 shows a standard Eclipse wired to a Model

U9500H Infiniti Transmitter.

Figure 13 shows a standard Eclipse wired to a Model

R8471H Controller.

Figure 14 shows the wiring terminal configuration for the

Eagle Quantum Premier Eclipse.

Figure 15 shows the Eclipse wired for benchtop testing/

programming using HART protocol.

NOTE

The Eclipse housing must be electrically
connected to earth ground. A dedicated earth
ground lug is provided for this purpose.

reMote Calibration wiring
If it is desired to initiate calibration using the remote

calibrate line, the use of the Det-Tronics Model PIRTB

Termination Box is highly recommended for optimum

ease of installation and calibration. The PIRTB module

includes a magnetic reed switch, indicating LED, and

wiring terminal block. Refer to “Remote Calibration

Option” in the “Description” section of this manual for

details.

Figure 16 shows the location of the wiring terminals, reed

switch and LED inside the calibration termination box.

See Figures 17 and 18 for wiring details.

WarnInG

Do not attempt to physically connect or touch
the calibration lead wire to DCV common in the
field to begin calibration. This practice is often
less than precise, and may result in a spark or
other undesirable results. For optimum ease of
installation and calibration, always utilize a Det-
Tronics junction box with magnetic reed-switch,
indicating LED, and termination block (Model
PIRTB).

Figure 3—Eclipse Wiring termination Compartment

with optional Relay Board Removed

FACTORY INSTALLED WIRING

TO RELAY BOARD

(DO NOT REMOVE)

CAPTIVE SCREWS (3)

RELAY TERMINAL BLOCK

A2133

Advertising