Det-Tronics OPECL Infrared Hydrocarbon Gas Detector User Manual

Page 14

Advertising
background image

12

95-8556

10.1

Module mounting options include:
• A vertical post with a nominal outside diameter of 4.5”

(11.43 cm). Acceptable outside diameter range is 4.0

to 5.0 inches. See Figure 5.

• For flat surface mounting, refer to Figure 6.

mounting Sequence
1. Attach the OPECL module to the pan-tilt mounting

plate and tighten the OPECL mounting bolts to 20

lb.-ft. minimum.

2. Install the lower mounting bracket.

3. Place the pan-tilt mounting plate on the lower bracket

and install the upper mounting bracket. Tighten the

mounting hardware to 20 lb.-ft. minimum. Tighten

the alignment bolts/nuts hand tight only.

noTe

Anti‑seize material (provided) must be applied
to the U‑bolt threads at the time of installation to
prevent galling.

24 vDC pOWER SUpply REqUIREmENTS
Calculate the total gas detection system power

consumption rate in watts from cold start-up. Select

a power supply with adequate capability for the

calculated load. Ensure that the selected power supply

provides regulated and filtered 24 Vdc power for the

entire system. If a back-up power system is required,

a float-type battery charging system is recommended.

If an existing source of 24 Vdc power is being utilized,

verify that system requirements are met.

noTe

If disconnection of power is required, separate
disconnect capability must be provided.

WIRINg CablE REqUIREmENTS
Always use proper cabling type and diameter for input

power as well as output signal wiring. 14 to 18 AWG

shielded stranded copper wire is recommended. For

EQP models, refer to the EQP system manual (95-8533)

for specific wiring requirements and recommendations.

Always install a properly sized master power fuse or

breaker on the system power circuit.

noTe

The use of shielded cable in conduit or shielded
armored cable is required for ATeX conformance.
In applications where the wiring is installed in
conduit, dedicated conduit is recommended. Avoid
low frequency, high voltage, and non‑signaling
conductors to prevent nuisance eMI problems.

CaUtIon

The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent
water ingress and/or maintain the explosion‑proof
rating.

MOUNTING BRACKET (2)

U-BOLT

*

(2)

PAN-TILT MOUNTING PLATE

OPECL MODULE

OPECL MOUNTING BOLT (2)

MOUNTING POST

B2305

*

APPLY ANTI-SEIZE MATERIAL TO U-BOLT

THREADS TO PREVENT GALLING.

Figure 5—OPECL Gas Detector Mounted to Vertical Post

MOUNTING BRACKET (2)

MOUNTING BOLT (2 PER BRACKET)

PAN-TILT MOUNTING PLATE

OPECL MODULE

OPECL MOUNTING BOLT (2)

FLAT MOUNTING SURFACE

A2306

Figure 6—OPECL Gas Detector Mounted to Flat Surface