ACCURACY—

Refer to the appropriate Appendix for details.

noTe

Misalignment will cause the manufacturer stated
Accuracy limits to increase, but remain within the
limits of en 50241‑1, ‑2, en 60079‑29‑4, and IeC
60079‑29‑4.

TEMPERATURE RANGE—

Operating: –55°C to +60°C (–67°F to +140°F)
Storage:

–55°C to +85°C (–67°F to +185°F)

Hazardous Locations: Refer to the appropriate

Appendix for correct ambient

temperature range:

Appendix A - FM

Appendix B - CSA

Appendix C - ATEX

Appendix D - IEC

HUMIDITY—

5 to 99% relative humidity; designed for outdoor

applications.

OPERATING PRESSURE—

91.5 - 105.5 kPA non-compensated.

MEASUREMENT RANGE—

0-5 LFL-meters.

INTERFERENCE RESISTANCE—

Immune to sun and flare radiation, tested to 800 ±50

W/m

2

≥ 3° to optical axis and common contaminants.

SELF-DIAGNOSTIC TEST—

Fail-Safe operation ensured by performing all critical

tests once per second.

MODULE HOUSING MATERIAL—

316 stainless steel (CF8M).

CONDUIT ENTRY OPTIONS—

Two entries, 3/4 inch NPT or 25 mm.

HART COMMUNICATION PORT—

An intrinsically safe port is provided on the receiver for

connecting a Rosemount/Emerson HART Communicator.
• Maximum separation distance between receiver and

communicator is 610 meters.

OPTICS PROTECTION—

Stainless steel brow provides a degree of protection

against windblown dirt and rain. Heated optics mitigate

against ice and dew formation.

WIRING—

Field wiring screw terminals are UL/CSA rated for up to

14 AWG shielded wire, and are DIN/VDE rated for 2.5

mm

2

wire. Screw terminal required torque range is 3.5–

4.4 lb.-in. (0.4-0.5 N·m). Receiver can be wired using 3

or 4 wires. Transmitter requires two wires (power only).

CERTIFICATION—

For complete approval details, refer to the appropriate

Appendix:

Appendix A - FM

Appendix B - CSA

Appendix C - ATEX

Appendix D - IECEx

Appendix E - Other Approvals