Warning, Caution, Dca-400ssk — generator start-up procedure (manual) – Multiquip DCA400SSK2 User Manual

Page 47

Advertising
background image

DCA-400SSK — PARTS AND OPERATION MANUAL (STD)— REV. #3 (09/17/01) — PAGE 47

WARNING:

Before Starting

Engine

1. Check the lubricating oil level prior to starting the engine.

Make sure the generator is level. The oil level must be
maintained between two notches on the dipstick.

2. When there is not enough lubricating oil, fill the crankcase

with high grade motor oil. Use a high quality detergent
oil classified CC or higher (See Table 11 on page 43).

3. Check the coolant level in the radiator and subtank.

Replenish with antifreeze as necessary. Always maintain
the coolant level between the FULL and LOW markings
on the coolant container. Be sure the radiator cap is
fastened securely.

4. Check the fuel level on the fuel gauge. If fuel is low, fill

the fuel tank with clean fresh unleaded automotive diesel.
If diesel spillage occurs, completely wipe up the spilled
fuel immediately.

Before Starting

Generator and Control Panel

CAUTION:

1. Be sure to disconnect the electrical load and switch the

main, load

main, load

main, load

main, load

main, load and G.F

G.F

G.F

G.F

G.F.C

.C

.C

.C

.C.I.

.I.

.I.

.I.

.I. circuit breakers (Figure 31) to

the “OFF” position prior to starting the engine.

NEVER start the engine with the main,

main,

main,

main,

main,

GFCI

GFCI

GFCI

GFCI

GFCI or load

load

load

load

load circuit breakers in the ON

position.

The engine's exhaust contains harmful
emissions. A L

A L

A L

A L

A LW

W

W

W

WA

A

A

A

AY S

Y S

Y S

Y S

Y S ventilate the

exhaust when operating inside tunnels,
excavations or buildings. Direct exhaust
away from nearby personnel.

Figure 31. Main, GFCI and

Load Circuit Breakers

Jacket Water Heater and Internal Battery Charger 120
VAC Output Receptacles (OPTIONAL)

This generator is equipped with two 120 VAC, 20 amp output
receptacles located on the output terminal panel, page 43,
Figure 14.

The purpose of these receptacles is to provide power via
commercial power to the jacket water heater and internal
battery charger.

These receptacles will ONLY function when commercial
power has been supplied to them (Figure 31). To apply
commercial power to these receptacles, a power cord of
adequate size will be required.

When using the generator in hot

hot

hot

hot

hot climates there is no reason

to apply power to jacket water heater. However, if the
generator will be used in cold

cold

cold

cold

cold climates it is always a good

idea to apply power to the jacket water heater at all times. To
apply power to the jacket water heater simply apply power
to the jacket water heater receptacle via commercial power
using an power cord of adequate size.

If the generator will be used daily, the battery should normally
not require charging. If the generator will be idle (not used)
for long periods of time, apply power to the battery charger
receptacle via commercial power using an power cord of
adequate size.

When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator's
internal battery charger. This will ensure that the engine will
not fail due to a dead battery.

CAUTION:

ALWAYS have power applied to the
generator's internal battery charger
when connecting the generator to a
isolation (transfer) switch. Remember

before connecting this generator to
any buildings electrical system, have
a licensed

licensed

licensed

licensed

licensed electrician perform the

installation of the transfer switch.

DCA-400SSK — GENERATOR START-UP PROCEDURE (MANUAL)