‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

PM130 PLUS Powermeter Series

77

Configuring Relay Outputs

The PM130 PLUS can be provided with two optional relay outputs. Each
relay can be operated either locally from the alarm/control setpoints in
response to an event or by a remote command sent through
communications. It can also be linked to an internal pulse source to
produce energy pulses.

Using the Front Display

Select reL from the main menu. This menu entry appears only if the
digital I/O module is plugged into the meter.

Use the UP and DOWN arrow buttons to scroll to the required relay.

To select a relay parameter:

1. Press the SELECT button to activate

the middle window.

2. Use the UP and DOWN arrow buttons to scroll to the required

parameter.

To change the parameter value:

1. Press the SELECT button to activate

the lower window.

2. Use the UP and DOWN arrow buttons to select the required

value.

3. Press ENTER to confirm the new parameter setting or press

ESC to discard changes.

You are returned to the middle window
and can configure other relay
parameters.

To store your new settings:

1. Press the ENTER button when the

middle window is highlighted.

You are returned to the upper window
and can select another relay output or
exit the menu.

2. Press ESC to exit the menu.

See Table 23

for the available relay outputs options.

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Relay Outputs tab.