Rockwell Automation 20G PowerFlex 750-Series EMC Plate and Cores - Frames 1…7 User Manual
Page 7
Advertising

Rockwell Automation Publication 750-IN006G-MU-P - February 2014
7
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
6
IP54
Step
Frame Procedure
6
continued
x4
x6
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded
T20
2.6 N•m (23.0 lb•in)
#1
The cable shield and drain wires must be
terminated at the shield clamp on the conduit
plate. The ground wire must be connected to
the PE stud in the drive; however, it should not
pass through the core.
Cabinet not shown