Control terminal block, Powerflex 523 control i/o wiring block diagram – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual

Page 11

Advertising
background image

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

11

PowerFlex 520-Series Adjustable Frequency AC Drive

Control Terminal Block

PowerFlex 523 Control I/O Wiring Block Diagram

04

05

06

01

02

03

11

12

13

14

15

C1

C2

Digital Common

DigIn TermBlk 05/Pulse

DigIn TermBlk 06

Stop

(1)

DigIn TermBlk 02/

Start/Run FWD

(2)

DigIn TermBlk 03/

Direction/Run REV

R1

R2

Relay N.O.

Relay Common

+24V DC

+10V DC

0-10V Input

Analog Common

4-20mA Input

RJ45 Shield

Comm Common

+24V

+10V

Typical

SNK wiring

Typical

SRC wiring

R1

11

12

13

14

15

C1

C2

R2

R3

01

02

03

04

05

06

Pot must be

1...10 k ohm

2 W min.

SNK

D

igital In

D

igIn T

ermBlk

05

Se

l

J7

J8

Pulse In

SRC

Digital

Input

SRC

SNK

R3

Relay N.C.

81

RS485

(DSI)

(1)

(2) Two wire control shown. For three wire control use a momentary input

on I/O Terminal 02 to command a start. Use a maintained input

for I/O Terminal 03 to change direction.

(3) Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time, an undetermined frequency reference will result.

IMPORTANT

I/O Terminal 01 is always a stop input. The stopping mode is determined by the drive setting.

The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this jumper when using I/O
Terminal 01 as a stop or enable input.