Protection, Dimensions [mm (in.), Mode of operation – Rockwell Automation 440N SensaGuard 18 mm Plastic Barrel Installation Instructions User Manual
Page 2: Status indicators, Mounting information, Nut torque specification, Minimum distance between sensors, Misalignment curve, 18 mm unit with 18 mm target, Protection dimensions [mm (in.)] mode of operation
2
Protection
Dimensions [mm (in.)]
Mode of Operation
Status indicators:
• “Power/Fault” LED illuminates green: Door/guard closed,
safety outputs active.
• “Power/Fault” LED illuminates red: Door/guard open,
safety outputs off.
• “Power/Fault” LED flashes red: Unit failure. See Diagnostic
section on page 3.
• “Power/Fault” LED flashes green: Safety inputs off.
Short-circuit Incorporated
Current Limitation
Incorporated
Overload
Incorporated
False Pulse
Incorporated
Transient Noise
Incorporated
Reverse Polarity
Incorporated
Overvoltage
Incorporated
Thermal Shutdown/Restart
Incorporated
Electrical Life
10 x 10
6
30 mm Actuator
48.92
[1.926]
19.81
[0.78]
22.22
[0.875]
48.92
[1.926]
19.81
[0.78]
22.22
[0.875]
30.40
[1.197]
16.84
[0.663]
3.17
[0.125]
4.57
[0.18]
2 places
Dia.
Sensor
18 mm Actuator
67.06
[2.640]
2.03
[.080]
M18X1
36.47
[1.436]
13.72
[0.54]
15.87
[0.625]
36.47
[1.436]
13.72
[0.54]
15.87
[0.625]
4.57
[0.180]
DIA
19.81
[0.78]
3.17
[0.125]
15.42
[0.607]
2 PLACES
Mounting Information
Use non-removable screws, bolts, or nuts to mount the switch and
actuator. Do not over torque the mounting hardware.
Position the switch and actuator so they are aligned with each
other.
Mount the switch and actuator to removable guard, door, or gate.
Keep the switch and actuator within the sensing range below.
This switch is not meant to be fully embedded in metal. Use the
stainless steel version (440N-Z21S17* or 440N-Z21U17*) for
embedding.
Nut Torque Specification
Plastic Barrel Switch: 2.26 N•m (20 in•lb)
Plastic Actuators: 2.26 N•m (20 in•lb)
Minimum Distance Between Sensors
Misalignment Curve
18 mm Unit with 18 mm Target
There must be a minimum spacing of 4 mm
(0.157 in.) if actuator and sensor face approaches
laterally. This will prevent false triggering due to
the side lobe areas.
18 mm Actuator
75 mm
Sensor
1
Sensor
2
30 mm Actuator
100 mm
Sensor
1
Sensor
2
Lateral Misalignment Tolerance—mm (in)
Face to Face Distance—mm
-15
(-0.59)
-10
(-0.39)
-5
(-0.19)
0
5
(0.19)
10
(0.39)
15
(0.59)
0
5
10
15
20
25
-25
(-0.98)
-20
(-0.787)
20
(0.787)
25
(0.98)
Side Lobe
Side Lobe
Assured Sensing
Distance
OFF
OFF
ON
Assured Sensing
Distance
OFF
IMPORTANT