Rockwell Automation 599-GR4_GR5 Service Disconnect Ground Kit for Bul 1494H and 1494HL Safety Switches User Manual
Rockwell Automation Equipment

599-GR4 (Disconnect Sizes 30A - 60A)
Enclosure Mounting Holes for Accessory Ground Kit
1. Holes are pre-punched for #10-32 thread cutting screws.
2. Holes are 2-7/16 inches apart.
3. Accessory mounting orientation will either be vertical or horizontal. Mounting depends on enclosure type and size.
599-GR5 (Disconnect Sizes 100A - 200A)
Service Disconnect Ground Kit Installation Instructions for
Bulletin 1494H (Heavy Duty) and Bulletin 1494HL (General Duty) Safety Switches
(Cat 599-GR4, -GR5)
42052-165 (Version 02)
Printed in U.S.A.
1
2
15 - 20 lb-in
41 - 45 lb-in
#6 - #4
32 - 35 lb-in
#14 - #10
36 - 40 lb-in
#8
Small Holes
60
o
or 75
o
C
#14 - #8 CU
#12 - #8 AL
15 - 20 lb-in
2
Large Holes
60
o
or 75
o
C
#14 - #4 CU
#6 - #4 AL
60
o
or 75
o
C
#12 - 1/0 CU / AL
120 lb-in
3/16" Hex
WARNING
To prevent electrical shock, disconnect from power source before installing or servicing.