Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual
Page 78

Speed Selection
Chapter 8
8-2
Priority 3 - Speed Select Input Is
The speed source programmed by Parameter 6 will be selected when the
True
speed select input at Terminal 27 is true. Parameter 6 may be programmed
- Parameter 6
for one of the following six sources:
Freq
P
R
Pr = - 0 if Parameter 6 = 0, Control Panel speed potentiometer
Pr = - 1 if Parameter 6 = 1, 0-10V DC input.
Pr = - 2 if Parameter 6 = 2, 4-20mA input.
Pr = - 3 if Parameter 6 = 3, pulse train input.
Pr = - 4 if Parameter 6 = 4, serial input.
Pr = - 5 if Parameter 6 = 5, remote speed potentiometer input.
Priority 4 - Speed Select Input Is
The speed source programmed by Parameter 5 will be selected when the
False
speed select input at Terminal 27 is false. The speed source programmed
- Parameter 5
by Parameter 5 will be the default speed source, the lowest speed source
priority. Parameter 5 may be programmed for one of the following six
sources:
Freq
P
R
Pr = - 0 if Parameter 5 = 0, Control Panel speed potentiometer.
Pr = - 1 if Parameter 5 = 1, 0-10V DC input.
Pr = - 2 if Parameter 5 = 2, 4-20mA input.
Pr = - 3 if Parameter 5 = 3, pulse train input.
Pr = - 4 if Parameter 5 = 4, serial input.
Pr = - 5 if Parameter 5 = 5, remote speed potentiometer input.