Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 50

Publication 1404-UM001D-EN-E - October 2004
3-24 Powermonitor 3000 Operations
Password
The password protects the unit against unauthorized commands or
configuration changes. Be sure to write down the new password and
keep it in a safe place. Range 0 to 9999, default 0000.
TIP
If you forget or lose your password, contact
Rockwell Automation Technical Support for
assistance. Refer to Rockwell Automation Support on
the back cover of this manual.
Table 3.7 Device Configurations Summary
Parameter Range
Default
User
Setting
Bas
ic
C
onfi
gurati
on
Wiring Mode
0 = Delta 3 CT
1 = Delta 2 CT
2 = Direct Delta 3 CT
3 = Direct Delta 2 CT
4 = Open Delta 3 CT
5 = Open Delta 2 CT
6 = Wye
7 = Single Phase
8 = Demo
6 = Wye
PT Primary
1 to 10,000,000
480
PT Secondary
1 to 600
480
CT Primary
1 to 10,000,000
5
CT Secondary
1 to 5
5
I4 Primary
1 to 10,000,000
5
I4 Secondary
1 to 5
5
Nominal System Voltage
(M6 and M8 only)
1 to 10,000,000
480