Upgrading your 1394 GMC Turbo Firmware
8
Publication 1394–6.3 – November 1997
4. Press the space bar on your keyboard to change NO to YES and
press Enter. The following message appears:
Application Password?
5. Type app and press Enter. You will not be able to see the letters
you are typing.
6. Press Enter after each of the following messages:
Inhibit Program Upload? NO
Edit AxisLink Config? NO
Edit DH–485 Config? NO
Edit Axis Setup Parameters? NO
Edit Axis Fault Action Configs? NO
Edit Direct Command Mode Config? NO
Edit Operator Interface Config? NO
Edit Runtime Display Config? NO
7. When the
Edit Serial Port Config? NO
message
appears, press the space bar on your keyboard to change NO to
YES and then press Enter. The following message appears:
Port A Baudrate? 9600
8. Press the space bar until 38400 appears and press Enter. The
following message appears:
Changing Baudrate...
9. Select Disconnect from the HyperTerminal Call menu.
10.From the HyperTerminal File menu, select Properties. The
Properties window appears.
11. Select Configure. The Port Settings window appears.
12.Select 38400 in the Bits per second field.
13.Select OK. The Properties window disappears.
14.Select Re–connect to establish communications using the higher
baud rate.