Counter Modes
21
Encoder x4
Encoder x4 mode is identical to x1, except this mode counts on the leading
and trailing edges of A and B to provide a greater number of pulse counts. The
greater the number of pulse counts the better the module can
determine position.
Input Z is used in Encoder mode only if a Store Count mode is enabled.
See
for details on the storage modes.
Encoder x4 Mode
Maximum frequency in Encoder x1 and x4 modes = 250 kHz (assuming
50% duty cycle), with a minimum pulse width at this frequency of 2 s. The
module assumes a 90° phase (A/B°) difference between channels.
Input A
Quadrature Encoder
1756-HSC Module
Input B
Input A
Input B
Input A
Input B
B Leads A 90°
A Leads B 90°
1
2
3 4
5 6 7
8
9 10 11 12
1
2
3
4
5
6
7
8
9
10
11
0
41689
Accumulated Count
in Present Value Tag
Directional Frequency
in Totalizer Tag
Positive Frequency
Negative Frequency
Input Z (optional)