1769-of8c, Input data file – Rockwell Automation 1769-XXXX Compact I/O Modules  User Manual

Page 142

Advertising
background image

142

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011

Chapter 3 I/O Memory Mapping

1769-OF8C

The following I/O memory mapping lets you configure the 1769-OF8C module.

Input Data File

For each module, slot

x, input data file words 3…10 contain the state of the

module’s output data (output data echo) file words 0…7. During normal
operation, these input words represent the analog values that the outputs are
directed to by the control program.

Enable
Ramping

Disabled

0

Enabled

1

System
Interrupt High
Clamp

Disabled

0

Enabled

(1)

1

System
Interrupt Low
Clamp

Disabled

0

Enabled

(1)

1

Enable
Channel

Disabled

0

Enabled

1

(1) These functions are not supported by all controllers, such as MicroLogix 1500, using any configuration method.

Refer to your controller manual for details.

Define

Indicate this

These bit settings

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Output Range
Select

-10 …+10V DC

0

0

0

0…5V DC

0

0

1

0…10V DC

0

1

0

1…5V DC

0

1

1

Output Data
Select

Raw/Proportional
Counts

0

0

0

Engineering Units

0

0

1

Scaled for PID

0

1

0

Percent Range

0

1

1

Define

Indicate this These bit settings

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

PF

S7

S6

S5

S4

S3

S2

S1

S0

1

D3

H3

U3

O3

D2

H2

U2

O2

D1

H1

U1

O1

D0

H0

U0

O0

2

D7

H7

U7

O7

D6

H6

U6

O6

D5

H5

U5

O5

D4

H4

U4

O4

3

Channel 0 Data Value

Advertising