Input filter times, Set the fault detect switch – Rockwell Automation 1797-IBN16 FLEX Ex NAMUR Input Module User Manual
Page 12

12 FLEX Ex NAMUR Input Module
Publication
1797-5.7 - March 2010
Input Filter Times
Set the Fault Detect Switch
A switch, located on the backside of the module, lets you select the action of
the module when a fault (wire off or short circuit) is detected. Switch position
1 determines the action for channels 0 to 3, position 2 for channels 4 to 7,
position 3 for channels 8 to 11, and position 4 for channels 12 to 15.
Set the switch:
• OFF to disable fault detection for the selected channels.
• ON to enable fault detection for the selected channels.
Bits
Description
Maximum
Filter Time
02
01
00
Filter Times 00…11 (00…13)
05
04
03
Filter Times 12…15 (14…17)
0
0
0
Filter Time 0 (default)
1 ms
0
0
1
Filter Time 1
1 ms
0
1
0
Filter Time 2
2 ms
0
1
1
Filter Time 3
3 ms
1
0
0
Filter Time 4
5 ms
1
0
1
Filter Time 5
9 ms
1
1
0
Filter Time 6
17 ms
1
1
1
Filter Time 7
33 ms
Bits 00
…
02 also control the filter times of all 16 fault alarm bits of read word 1 when
module is in fault mode
.
OFF
1
2
3 4
OFF
1 2 3 4