Certification Specific ControlNet Ex System Diagrams
The following pages include certification specific ControlNet Ex system
diagrams and notes pertaining to these diagrams. Select either CENELEC,
UL, C-UL, or FM and follow the requirements of that diagram as you
configure and install your system.
CENELEC Installation Label
A label with this system marking must be attached near the main components
of the system. If the system is installed in a cabinet, this label must be fixed
inside the cabinet.
CENELEC 1797-ACNR15 I/O Entity Parameters
Terminals
U
o
(V)
I
o
(mA)
Groups
C
o
(
μF)
L
o
(
μH)
Male Bus
Connector
5.4
400
IIB/IIC
65
10
0102
ControlNet Ex System
Allen-Bradley
Attention!
Avoid electrostatic charging!
-20
0
C <= Ambient Temperature <= +70
0
C
1 Allen-Bradley Dr.
Mayfield Hts., OH USA
DMT 99 ATEX E 065 X
II (1)2G Ex ia ib IIC