Wire the safe-off (so) connector, D in, Table 36 – Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual
Page 90

90
Rockwell Automation Publication 2099-UM001D-EN-P - December 2012
Chapter 4
Connect the Kinetix 7000 Drive System
Table 36 - DC Input Power Connections
Wire the Safe-off (SO) Connector
Wire the Safe-off connections to your Kinetix 7000 drive as described in
. See Safe-off (SO) Terminal Block Connections for more information.
Table 37 - Safe-off Connections
Kinetix 7000
Drive Cat. No.
Signal Description
Terminal(s)
Recommended Wire Size
mm
2
(AWG)
Torque
N
•
m (lb
•
in)
2099-BM06-S
2099-BM07-S
2099-BM08-S
DC+
DC-
DC+
DC-
25…2.5 (3…14)
1.8 (16)
2099-BM09-S
DC+
DC-
DC+
DC-
50…4 (1/0…12)
3.6 (32)
2099-BM10-S
DC+
DC-
DC+
DC-
70…10 (2/0…8)
15 (133)
2099-BM11-S
2099-BM12-S
DC+
DC-
DC+
DC-
100…10 (4/0…8)
12 (104)
IMPORTANT
Terminals 8 and 9 (24V+ and Common) are only used by the motion-
allowed jumper. When using the Safe-off feature, the 24V supply must
come from an external source.
Signal
Terminal
Recommended Wire Size
mm
2
(AWG)
Strip Length
mm
2
(in.)
Torque
N
•
m (lb
•
in)
FDBK2+
1
0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)
7.0 (0.275)
0.235 (2.0)
FDBK2-
2
FDBK1+
3
FDBK1-
4
ENABLE2+
5
ENABLE-
6
ENABLE1+
7
SO_24VDC
8
SO_COM
9