Minimum mounting clearances, Operating temperatures – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9-14 Drives Installation - A4 Size User Manual
Page 134
Advertising

10-2
Frame 13 Installation
Minimum Mounting
Clearances
Operating Temperatures
Frame 13 drives require a minimum of 4200 m
3
/h (2472 cfm) of cooling air
for the Inverter unit and 1150 m
3
/h (677 cfm) of cooling air for each
Converter unit.
800 mm
(31.50 in.) Min.
200 mm
(8.0 in.) Min.
1600 mm, Style “A” Enclosure Shown.
PowerFlex
Drive
Voltage Class
Amp Rating
Surrounding Air Temperature
Normal Duty
Heavy Duty
700H
All
All
0 to 40
°
C (32 to 104
°
F) 0 to 40
°
C (32 to 104
°
F)
700S
400/480V AC
(540/650V DC)
All
0 to 40
°
C (32 to 104
°
F) 0 to 40
°
C (32 to 104
°
F)
600/690V AC
(810/932V DC)
920, 1030
0 to 40
°
C (32 to 104
°
F) 0 to 40
°
C (32 to 104
°
F)
600/690V AC
(810/932V DC)
1180
0 to 35
°
C (32 to 95
°
F)
0 to 35
°
C (32 to 95
°
F)
Advertising