Logic Command/Status Words
C-1
A
PPENDIX
C
Logic Command/
Status Words
Appendix C provides the definitions of the Logic Command/Logic
Status words that are used for some products that can be
connected to the Interbus module. If you do not see the Logic
Command/Logic Status for the product that you are using, refer to
your product’s documentation.
Logic Command Word
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command
Description
x Stop
0 = Not Stop
1 = Stop
x
Start
1
0 = Not Start
1 = Start
x
Jog
0 = Not Jog
1 = Jog
x
Clear Faults
0 = Not Clear Faults
1 = Clear Faults
x x
Direction
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
x
Local Control 0 = No Local Control
1 = Local Control
x
MOP
Increment
0 = Not Increment
1 = Increment
x x
Accel Rate
00 = No Command
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate
x
x
Decel Rate
00 = No Command
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate