Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 113

Publication GMSI10-UM003D-EN-P - May 2010
105
Instance 101 - XM-123 Module Measurements
This is the default assembly that is sent within the I/O Poll Response message
when an I/O Poll request is received from a DeviceNet master.
Instance 102 - XM-123 Module Measurements
This is an alternate assembly for the I/O Poll Response message.
3
Relay 4
Status
0
Alarm 8 Status
Alarm 7 Status
4
Relay 5
Status
0
Alarm 10 Status
Alarm 9 Status
5
0
0
Alarm 12 Status
Alarm 11 Status
Table C.10 Instance 100 Data Format (Alarm and Relay Status Values Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Table C.11 Instance 101 Data Format (XM-123 Measurement Values Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 - 3
Channel 1 Tracking Magnitude value
4 - 7
Channel 2 Tracking Magnitude value
8 - 11
Speed value
12 - 15
Channel 1 Overall value
16 - 19
Channel 2 Overall value
20 - 23
Channel 1 Tracking Phase value
24 - 27
Channel 2 Tracking Phase value
28 - 31
Channel 1 DC Bias value
32 - 35
Channel 2 DC Bias value
Table C.12 Instance 102 Data Format (XM-123 Measurement Values Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 - 3
Channel 1 Bandpass value
4 - 7
Channel 2 Bandpass value
8 - 11
Channel 1 Overall value
12 - 15
Channel 2 Overall value
16 - 19
Speed value
20 - 23
Channel 1 DC Bias value
24 - 27
Channel 2 DC Bias value
28 - 31
0
32 - 35
0