Mustang series, Pump control valve with rate-of-flow feature – Watts M1113-41 User Manual
Page 2
8550 Hansen Road
•
Houston, Texas 77075
•
(Ph) 713.943.0688
•
(Fx) 713.944.9445
•
www.wattsacv.com
01/05
R
Mustang Series
PUMP CONTROL VALVE with
RATE-OF-FLOW FEATURE
M113-41 or M6113-41 (Globe)
M1113-41 or M61113-41 (Angle)
Installation Guidelines
• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Install Orifice Plate Assembly (provided) 3 to 5 pipe diameters downstream of the valve with the sensing
connections offset from top of pipeline to avoid air accumulation. The Orifice Plate Assembly should not
be installed next to a butterfly valve.
• Connect Orifice Plate Assembly to Rate-of-Flow Pilot using 3/8” diameter minimum copper tubing (field
installed) in accordance with factory piping schematic.
• Connect Solenoid and Limit Switch to appropriate pump control panel locations and power source in
compliance with local electrical codes.
Other Watts ACV Pump Control Valves
M113-21 / M6113-21 Pump Control Valve
M113-19 / M6113-19 Pump Control Valve with Backpressure Feature
M113-29 / M6113-29 Pump Control Valve with Pressure Reducing Feature
M513-5 / M6513-5
Pump Control Valve
M513-AK / M6513-AK Pump Control Valve with High Capacity Pilot System
M513-6 / M6513-6
Deep Well Pump Control Valve
M513-14 / M6513-14 Deep Well Pump Control Valve with Pressure Relief Feature