CCI Thermal Technologies XT-311 - Defender Explosion-Proof Thermostat User Manual
Defender, Installation instructions, Thermostat for use in hazardous locations
Installation Instructions
Models:
Feed-thru Models
XT-311 SPST
XT-312 SPDT
ISO 9001
HEAT
COOL
COM.
2
1
3
-
T
X
1
.
G
I
F
L1
L2
HEAT
COOL
COM.
COOLING EQUIPMENT
s
l
e
d
o
M
ll
A
2
.
G
I
F
11936.Rev.1.00
L1
L2
Thermostat for use in hazardous locations
Defender
®
22 Amps Res., 480 VAC Max.; 1/2 HP @ 125 VAC, 1 HP @ 250 VAC Class I, Divisions
1 & 2, Groups C & D; Class II, Division 1, Groups E, F & G; Class II, Division 2, Groups
F & G; Class III; Class I, Zones 1 & 2, Groups IIA & IIB.
CAUTION: Electrician must have experience with Hazardous Location equipment.
Disconnect and lock off power supply before wiring or servicing. All wiring must comply
with local codes and ordinances.
1. Mount thermostat
approximately 5’ (1.5m)
above the floor where
average room temperature
will be sensed and air
circulates freely. Keep
thermostat away from hot
and cold surfaces.
2. Wire switch terminals as per
Fig. 1 or 2.
3. Install the cover using the 4
bolts supplied and tighten
4. Fill any unused conduit
opening using plug supplied.