Installation Instructions

Part No. 00EFN900003200A

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5

Configuration (All Sizes)

. . . . . . . . . . . . . . . . . . . . . . . . . 2

Test Pump Control Output

. . . . . . . . . . . . . . . . . . . . . . . 2

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning

equipment can be hazardous due to system pressures, electrical

components, and equipment location.

Only trained, qualified installers and service technicians

should install, start up, and service this equipment.

When working on air-conditioning equipment, observe

precautions in the literature, on tags, stickers, and labels

attached to the equipment.

Follow all safety codes. Wear safety glasses and work

gloves. Use care in handling and installing this accessory.

GENERAL

This accessory provides required components to integrate

control of an external pump into the 30XA chiller control. As

part of the chiller control, the pump will be commanded on

or off based on the chiller operation. The pump will also be

monitored through the chiller control for its status. Any corre-

sponding alarms will be reported if the pump does not operate

normally.

One accessory package is required for 30XA080-500 units.

INSTALLATION

Examine the package contents for correct part numbers. If

any of the components are missing or damaged, file a claim

with the shipping company and notify your Carrier representa-

tive. See Table 1 for accessory package contents. Refer to

Fig. 1-3 for wiring details, and see Fig. 4 and 5 for board

mounting locations.

The following material is field-supplied:

• 18 AWG (American Wire Gage) wires for pump control

wiring

• Wire terminals and wire ties

Table 1 — Accessory Package Contents

To install the 30XA external pump accessory complete the

following steps.

1. Disconnect unit power.
2. Set the board address switch on the pump board as shown

in Fig. 2. Mount the pump board in the main control panel

with the No. 8 screws. See Fig. 4 and 5 for the board

mounting location.
NOTE: Mounting standoffs are required for 30XA080-

120 units, 200/230, 380v and 30XA140-500 units, all

voltages.

3. Mount the 24 v circuit breaker (CB14) in the CB14

mounting hole on the display mounting bracket. See

Fig. 4 and 5 for the mounting hole location. The display

mounting bracket can be easily removed by loosening the

four mounting screws on the corners.

4. Connect the 24 v power from TB10-X1 (30XA080-120

units, 460/575 v only) or TB11-X1 (all other units and

voltages) to CB14 with a red wire in the harness assembly

(Item 2). Find a 2-pin plug marked J1-11,12 with a red

wire and a brown wire in the harness assembly. Connect

the plug to the pump board J1. On the other end, connect

the red wire from the plug to CB14 and the brown wire to

TB10-X2 (30XA080-120 units, 460/575 v only) or

TB11-X2 (all other units and voltages). Refer to Fig. 1.

5. Connect TB5-11, 13 to pump board CH1 and TB5-13, 15

to pump board CH2 per Fig. 2 with the harness assembly

provided (Item 2). Use the pins on the back of TB5.
NOTE: If only one pump is available in the system (no

backup pump), the wiring for pump board CH2 is not

required.

6. For 30XA080-120, 200/230 v, 380 v and all 30XA140-500

units, disconnect the 3-pin plug on MBB (main base board)

J9B (or EMM board J9A) for communication and plug it in

to the pump board J9. Use the communication cable assem-

bly (Item 6) to connect between pump board J9 and MBB

J9B (or EMM board J9A when EMM board exists). The

communication cable in the TH70400864 harness will not

be used. For 30XA080-120, 460 v, and 575 v units, connect

the 3-pin plug of the communication cable in the harness

assembly (Item 2) to the pump board J9 and splice the other

end of the cable to the communication network using the

wire nuts provided (Item 7). Be sure to splice the wires

with the same color together to ensure correct polarity.

Be sure power to equipment is shut off before performing

installation, maintenance or service. Lock out and safety-

tag all disconnects. Be aware that there may be more than

one disconnect. Serious personal injury from electric shock

could result.

ITEM

NO.

DESCRIPTION

PART NO.

QUANTITY

1

Pump Board

32GB500432E

1

2

Harness Assembly

TH70400864

1

3

24 V Circuit Breaker (CB14)

HH83ZB001

1

4

No. 8 Screw

A6X10004352

4

5

Board Mounting Standoff

A6X10004434

4

6

Communication Cable Assembly

TH70400852

1

7

Wire Nut

HY89TB010

5

8

2-Pin Connector

1757019

1

30XA080-500

External Pump Control

Accessory